Fuel
Systems
Appendix A — Fuel System Standard
15.0 — Lab Examination No. 11
Fuel System Static Pressure Test cont'd
15.5.8 Connect either an air
or GN2 pressure source capable of supplying a regulated pressure
of 0–10-psig to the pressure supply adapter in the fill
hose. A pressure gauge or a manometer shall be connected to
a tee in the pressure supply line as close as possible to
the pressure supply adapter. A pressure gauge shall have a
range not exceeding three times the test pressure as required
by paragraph 15.5.7. The
relief valve shall be set at 1.5 ±0.5-psi above the
test pressure as required by Paragraph 15.5.7.
FIGURE:
Procedure — Test Schematic
15.5.9 Verify that the system
is configured similar to the Test Schematic and is ready for
testing:
a. Pressure supply valve closed.
b. Pressure supply regulator fully decreased (ccw).
c. Fuel shutoff valve between main tank and any auxiliary
tank full open (if any).
d. Any valve between the main tank and the carburetor full
open (if any).
15.5.10 Open the pressure supply
valve. Slowly increase the pressure supplied to the system
by turning the regulator cw for monitoring the pressure gauge
or manometer. Increase the pressure at a rate not to exceed
1/2-psi per minute until the required test pressure is reached
as determined by Paragraph 15.5.7
and indicated on the pressure supply gauge or the manometer.
15.5.11 Maintain this test
pressure ±1/4-psi for at least 5 minutes and allow
the system to stabilize. During this period verify that there
is no audible leakage in the system.
Note:
At any time during the test when leakage is detected, the
points of leakage should be noted and documented, and the
system should be vented to 0-psig. If the leakage is due entirely
to the test hardware, the leak shall be corrected and the
test rerun starting with Paragraph 15.5.9. If the leakage
is in the fuel system and determined to be caused solely by
the improper installation of a component as determined by
the test engineer (such as a hose clamp left off or a loose
B-nut), the installation may be corrected to the proper specification
and the test rerun starting with Paragraph 15.5.9. Any discrepancies
shall be so documented in the procedure.
15.5.12 Verify that the entire
fuel system has been pressurized as evidenced by the pressure
gauge readings at the auxiliary fuel tank, if installed, and
at the engine fuel inlet. These gauges will not necessarily
indicate much less than the pressure as the pressure supply
gauge and there is no requirement for them to do so. The engine
fuel inlet pressure gauge may indicate much less than the
pressure supply gauge, depending on the anti-siphon valve
installed and the other components in the fuel feed line.
Any positive indication of pressure is acceptable. If 0-psig
is indicated, the test shall be halted until the situation
has been examined, and the proper corrective action is determined
by the test engineer.
15.5.13 With the pressure supply
gauge indicating the required test pressure ±1/4-psi
and stable, close the pressure supply valve and record the
pressure indicated. This is the initial pressure decay reading.
15.5.14 Observe the pressure
supply gauge or manometer for a period of five minutes for
tanks whose fuel capacity is 50-gal. (189.3 l) or less. For
tanks over 50-gal. (189.3 l), an additional minute shall be
added to the five minutes for each 10-gal. (37.9 l) increment
or fraction thereof.
Example:
A 61-gal. (230.9 l) tank, or a 70-gal. (265 l), tank shall
be observed for seven (7) minutes.
At the end of the required time, record the
pressure indicated on the pressure supply gauge. This is the
final reading. The pressure reading shall have decreased from
the initial pressure reading less than 1/4-psi if a pressure
gauge was used or less than 0.5 in. (1.3 cm) if an Hg manometer
was used.
15.5.15 If the system pressure
has decayed more than allowed from the initial pressure reading,
verify no leakage exists in the test hardware using a leak
detection solution and reject the fuel system if required
by Paragraph 15.5.11. Otherwise, correct the problem and rerun
the test starting with Paragraph 15.5.13. Document any discrepancy.
15.5.16 Perform a complete
leak test of the entire fuel system using a leak detection
solution. The test shall include:
a. fuel tank(s) and vent connections except
at the hull or deck fitting(s)
b. fuel tank(s) fuel indicator fitting
c. fuel tank(s) feed line connection
d. any other connection or fitting on the fuel tank(s)
e. feed line between main tank and auxiliary tank, if installed,
and any valves or
components including connections and fittings
f. feed line between main tank and the carburetor and any
valves or components such as anti-siphon valve, shutoff
valve, fuel fittings and/or strainer, fuel pump including
connections and fittings
g. any other line or component which is part of the fuel
systems
No leakage in the system is allowed. If leakage
is detected, the fuel system shall be rejected. If no leakage
is detected, the fuel system shall be deemed acceptable according
to the requirements of this procedure. Record whether or not
any leakage was found and the location(s).
Previous |
Next
|