183.584 - Shock test

(e) (1) If the tank is not labeled under Sec. 183.514(b)(8) for installation aft of the half-length of the boat, apply 1000 cycles of 25g vertical accelerations at a rate of 80 cycles or less per minute. The duration of the acceleration pulse must be between 6 and 14 milliseconds.

FIGURE 41 - Fuel Tank Installed Anywhere in the Boat

The test should be monitored with suitable instrumentation mounted as near to the center of gravity of the tank as is possible.

The tank should be inspected during the shock test to detect an obvious failure. This is a visual inspection, and should a failure of any type occur, the tank should be rejected.