|
|
Fuel
Systems
Manufacturer Requirements
FEDERAL LAW
183.568 - Anti-siphon protection
Each fuel line from the fuel tank to
the fuel inlet connection on the carburetor must:
(a) Be above the level of the tank top;
or
(b) Have an anti-siphon device or an electrically operated
fuel stop valve:
(1) At the tank withdrawal fitting;
or
(2) Installed so the line from the fuel tank is above
the top of the tank; or
(c) Provided that the fuel tank top is
below the level of the carburetor inlet, be metallic
fuel lines meeting the construction requirements of
Sec. 183.538 or “USCG
Type A1” hose, with one or two manual shutoff
valves installed as follows:
(1) Directly at the fuel tank connection
arranged to be readily accessible for operation from
outside the compartment, and
(2) If the length of fuel line from the tank outlet
to the engine inlet is greater than 12 feet, a manual
shutoff valve shall be installed at the fuel inlet
connection to the engine.
|
"Anti-siphon protection” is a term
applied to the means of preventing the siphon action of permitting
fuel to continue to flow out of the fuel tank in the event
there is a break or rupture in a fuel distribution line, or
if a fitting in the fuel line loosens, creating a leak.
"Anti-siphon protection” may be
accomplished by one or more of the following methods:
(a) Keep all parts of the fuel line from
the fuel tank to the fuel line connection at the carburetor
above the level of the top of the fuel tank. The tank top
level is determined with the boat in its “static floating
position.” Practically, the fuel pump and fuel filter(s)
must also be above the tank top.
(b) Install an anti-siphon device at the
tank withdrawal fitting. The fuel distribution line may
then run below the level of the tank top. A filter may be
installed between the fuel tank withdrawal fitting and the
anti-siphon device.
NOTES:
- Some anti-siphon devices are spring
loaded check valves. These valves have a specific cracking
pressure and provide protection up to a specific head. Therefore,
the anti-siphon valve must be selected or ordered to protect
against the siphon head for a particular installation.
- Too high a cracking pressure may
cause vapor lock. This has become an increasing problem
with reformulated gasoline (RFG). Be sure to select the
correct cracking pressure.
- Some anti-siphon devices involve
a bleed hole in the fuel pick-up tube, near the top of the
fuel tank. The size of the hose is critical for a particular
application. Each installation using this type of protection
must be evaluated to assure its effectiveness. Too large
a hole will bleed excessive air into the fuel flow effecting
engine operation. Too small a hole may not stop fuel flow
in the event of a fuel leak. This installation is used very
infrequently because of inherent problems that may result.
(c) Install an anti-siphon device
at a location where a line from the fuel tank will no
longer remain above the fuel tank top level. The anti-siphon
device will then protect the portion of the line that
must run below the tank top level. The portion of the
line that is above the fuel tank top level will be automatically
taken care of.
(d) Install an electrically operated
fuel stop valve at the fuel tank withdrawal fitting. This
valve requires electrical power to open and must be connected
to operate only when the ignition switch is on. A filter
may be installed between this valve and the fuel tank
withdrawal fitting. Electrically operated fuel stop valves
must comply with 183.528.
(e) Install an electrically operated
fuel stop valve at the point in a fuel line where it must
run lower than the fuel tank top level. This valve requires
electrical power to open and must be connected to operate
only when the ignition switch of the engine it serves
is on. A filter may be installed between this valve and
the fuel tank withdrawal fitting. Electrically operated
fuel stop valves must comply with 183.528.
NOTES:
- Fuel stop valves used in the fuel
system, whether electrically operated or manually operated,
must withstand the 2-1/2 minute fire test in accordance
with 183.590.
- Anti-siphon devices are not required
to meet a fire test.
- The fuel stop valve is required to
be directly at the fuel tank connection by 183.568(c)(1)
and must be installed so that it can be operated from outside
the compartment. This can be accomplished with a reach rod
or a long valve stem. The installation of an access panel
over the valve is also permitted. However, once open, the
valve must be immediately accessible inside the panel so
that the operator does not have to reach through fire to
shut off the fuel.
FIGURE
34 - Anti-Siphon Protection
TO COMPLY WITH THE LAW
- Is the fuel distribution line above
the fuel tank top level?
- If not, is an anti-siphon device or
an electrically operated fuel stop valve installed
at the fuel tank withdrawal fitting?
- If not, is an anti-siphon device or
an electrically operated fuel stop valve installed
at the point where the fuel distribution line goes
below the fuel tank top level?
|
Previous |
Next
|
|