TABLE 5A
Allowable Amperage of Conductors of 50 Volts or More When No More Than 2 Conductors are Bundled
| No More Than 2 Conductors Are Bundled For 50 Volts and Over |
|||||||||||||
| Temperature Rating Of Conductor Insulation |
|||||||||||||
|
Conductor Size (AWG) |
60¡C |
75¡C |
80¡C |
90¡C |
105¡C |
125¡C |
200¡C |
||||||
| Outside |
Inside |
Outside |
Inside |
Outside |
Inside |
Outside |
Inside |
Outside |
Inside |
Outside |
Inside |
Outside
or Inside |
|
| 18 |
10 |
5.8 |
10 |
7.5 |
15 |
11.7 |
20 |
16.4 |
20 |
17.0 |
25 |
22.3 |
25 |
| 16 |
15 |
8.7 |
15 |
11.3 |
20 |
15.6 |
25 |
20.5 |
25 |
21.3 |
30 |
26.7 |
35 |
| 14 |
20 |
11.6 |
20 |
15.0 |
25 |
19.5 |
30 |
24.6 |
35 |
29.8 |
40 |
35.6 |
45 |
| 12 |
25 |
14.5 |
25 |
18.8 |
35 |
27.3 |
40 |
32.8 |
45 |
38.3 |
50 |
44.5 |
55 |
| 10 |
40 |
23.2 |
40 |
30.0 |
50 |
39.0 |
55 |
45.1 |
60 |
51.0 |
70 |
62.3 |
70 |
| 8 |
55 |
31.9 |
65 |
48.8 |
70 |
54.6 |
70 |
57.4 |
80 |
68.0 |
90 |
80.1 |
100 |
| 6 |
80 |
46.4 |
95 |
71.3 |
100 |
78.0 |
100 |
82.0 |
120 |
102.0 |
125 |
111.3 |
135 |
| 4 |
105 |
60.9 |
125 |
93.8 |
130 |
101.4 |
135 |
110.7 |
160 |
136.0 |
170 |
151.3 |
180 |
| 3 |
120 |
69.6 |
145 |
108.8 |
150 |
117.0 |
155 |
127.1 |
180 |
153.0 |
195 |
173.6 |
210 |
| 2 |
140 |
81.2 |
170 |
127.5 |
175 |
136.5 |
180 |
147.6 |
210 |
178.5 |
225 |
200.3 |
240 |
| 1 |
165 |
95.7 |
195 |
146.3 |
210 |
163.8 |
210 |
172.2 |
245 |
208.3 |
265 |
235.9 |
280 |
| 0 |
195 |
113.1 |
230 |
172.5 |
245 |
191.1 |
245 |
200.9 |
285 |
242.3 |
305 |
271.5 |
325 |
| 00 |
225 |
130.5 |
265 |
198.8 |
285 |
222.3 |
285 |
233.7 |
330 |
280.5 |
355 |
316.0 |
370 |
| 000 |
260 |
150.8 |
310 |
232.5 |
330 |
257.4 |
330 |
270.6 |
385 |
327.3 |
410 |
364.9 |
430 |
| 0000 |
300 |
174.0 |
360 |
270.0 |
385 |
300.3 |
385 |
315.7 |
445 |
378.3 |
475 |
422.8 |
510 |
| There is NO limit on conductors in a bundle for under 50 volts. |
|||||||||||||