Table of Contents:

Overview

Part 1

Part 2

Part 3

Electrical

Electrical - Table of Contents

Introduction

General

Manufacturer Requirements

Typical Wiring Diagrams

Figures & Tables

Appendix

Fuel Systems

Ventilation

Safe Loading

Flotation

Downloads

Electrical Systems

Manufacturer Requirements

FEDERAL LAW

183.460 - Overcurrent Protection: Special Applications

(a) Each ungrounded output conductor from a storage battery must have a manually reset, trip-free circuit breaker or fuse, unless the supply conductor is in the main power feed circuit from the battery to an engine cranking motor. The circuit breaker or fuse must be within 72 inches of the battery measured along the conductor, unless, for boats built prior to August 1, 1985, the circuit has a switch that disconnects the battery.

Ungrounded conductors connected to a storage battery, other than cranking motor conductors, must have overcurrent protection in accordance with 183.455(a). This section of the regulation provides an exception to 183.455(b) which allows the overcurrent protection location for the battery cable, as described, to be a distance from the connection at the battery (Section 182.455(b) requires the overcurrent protection to be at the power source). The distance from the battery connection depends on whether or not the overcurrent protection device is equipped with a switch.

  • Overcurrent protection without a switch must be located within 72 inches of the battery connection. See Figure 25.
  • Overcurrent protection with a switch may be located anywhere along the battery cable, if the boat was built before August 1, 1985. See Figure 25.

The only exception to the overcurrent protection requirement for conductors is for cranking motor power conductors, as excepted in 183.455(e). Schematics of typical main supply circuits are shown in Figure 25.

TO COMPLY WITH THE LAW

Except for the power supply conductors to the engine cranking motor:

  • Is there a manually reset, tripfree circuit breaker or fuse in each ungrounded output conductor from each storage battery?
  • Is the circuit breaker or fuse within 72 inches of the battery, measured along the conductor? or
  • If the boat was built prior to August 1, 1985, is there a switch in the circuit to disconnect the battery?

Previous  | Next

 

USCG red rod