Electrical
Systems
Manufacturer Requirements
FEDERAL LAW
183.435 - Conductors in Circuits of
50 Volts or More
(a) Each conductor in a circuit that
has a nominal voltage of 50 volts or more must be:
(1) A conductor that has insulation
listed and classified as moisture resistant and flame
retardant in Article 310, NFPA No. 70, National Electric
Code; or
(2) A flexible cord type SO, STO, ST,
SJO, SJT, or SJTO listed in Article 400, NFPA No.
70, National Electric Code;
(3) A conductor that meets IEEE Standard
45;
(4) A conductor that meets UL Standard
1426.
|
This section applies only to wiring in circuits
of 50 volts or more. However, conductors meeting any one of
these alternate requirements will also qualify for circuits
of less than 50 volts. The alternating current (AC) systems
of 120 and 240 volts are the systems normally in use on boats
to which these requirements apply.
Paragraphs (a)(1), (a)(3) and (a)(4) apply to
conductors in general, while (a)(2) applies specifically to
various types of flexible cords.
Types
Conductors for circuits of 50 volts or more
may be used if they:
(a) are classified as “moisture resistant”
and “flame retardant” in Article 310 of the
National Electrical Code, such as those designated:
THW, TW, THWN, XHHW, MTW or;
(b) are flexible cords type SO, STO ST, SJO,
SJT, or SJTO, listed in Article 400 of the National Electrical
Code, (see Table 6);
(c) are conductors that meet the IEEE Standard
45, such as those
designated:
R, B, T, V, AV, TA, M, S; or
(d) are conductors that meet the requirements
of UL Standard 1426.
There may be other cords or wires on the market,
such as S, SE, SEO, SJE, SJEO, SJOO, SJTOO, and SOO, which
have been accepted by the U.S. Coast Guard. If you are considering
a cord or wire other than one listed above, check with the
supplier for a copy of the Coast Guard’s letter of acceptance.
Conductors, as purchased, often do not indicate
whether or not they conform with the above requirements and
standards. If the conductors or their packaging are not so
marked, then an alternative means of assurance of compliance
should be obtained. Certification of compliance by the cable
vendor is one acceptable means.
Sizing
Table 5 is used to select the size of conductors.
Correction factors are provided for conductors used in engine
spaces (Note 1) and also for bundling of conductors used in
circuits of 50 volts or more (Note 2).
Tables 5A through 5E have been developed for
this guideline, and include corrected values, so it is not
necessary to perform the calculations required if using Table
5. Select the proper table according to the number of 50 volts
or more current carrying conductors in a bundle and then read
the wire gauge needed according to the temperature rating,
location of the conductor and the circuit lead. Refer to “How
to Select a Conductor” which follows, for further information.
Conductors, as purchased, often do not display
the temperature ratings of conductor insulation. If the conductors
or their packaging are not so marked, then an alternate means
of assurance of compliance should be obtained. Certification
of compliance by a vendor is one acceptable means.
How to Select a Conductor
FACTORS
To select a conductor in accordance with the
regulation, there are a number of factors to consider:
- Temperature rating of conductor insulation.
- Current rating required for the circuit.
- Is the conductor in an engine space?
- Is the system voltage less than 50 volts,
or is it 50 volts or more?
- How many conductors will run in a bundle?
- What type of conductor is permitted; i.e.
SAE, NEC, IEEE, UL or other?
PROCEDURE
1. Determine the circuit load - add up the rated
loads of the electrical devices in the circuit.
The boat manufacturer will have to determine
the circuit loads in the boat in order to properly size conductors
and the related overcurrent protection. If a conductor is
supplying a single load, sizing the conductor and its overcurrent
protection is simple. If, however, a single conductor is supplying
multiple or cumulative loads, such as a distribution panel,
the boat manufacturer does not have to size the conductor
to carry the summation of all the loads connected to the panel,
but only a percentage of these loads, due to loading factors.
The regulation does not require that a conductor be sized
to carry the full load of a distribution panel, but does require
that proper overcurrent protection be provided for the size
of the conductor chosen.
The boat manufacturer has a choice between the
extremes of providing a conductor that can carry the full
load, and using a smaller conductor that is adequate because
of load factors, but still large enough to avoid nuisance
tripping of its overcurrent protection.
Of course, whichever size conductor is used,
it must be protected with the proper size overcurrent protection.
It must also be noted that 183.425(b) restricts the maximum
load a conductor may carry to that specified in Table 5, except
for intermittent higher currents. (See 183.455 and 183.460
for Overcurrent Protection Requirements).
2. Decide what temperature rating of conductor
will be used.
3. If in an engine space, apply the correction
factor to the amperage values in Table 5 for the temperature
rating selected. Tables 5A through 5E provide a column of
corrected amperages for use in engine spaces.
4. If the electrical system is 50 volts or more,
determine the number of current carrying conductors (grounding
conductors are not normally current carrying) that will be
bundled together. If more than two, select the appropriate
correction factor and apply it to the amperage values in Table
5 or as corrected for use in engine spaces. Tables 5B through
5E provide corrected amperages for various numbers of conductors
in bundles and also provide a column for conductors used in
engine spaces.
5. In Table 5 or Tables 5A through 5E under
the column for the selected temperature rating of the conductor,
find the amperage that, when the necessary correction factors
are applied (not needed when using Tables 5A through 5E) equals
or exceeds the circuit load.
6. Read the gauge of the conductor to be used.
7. Select a conductor of STRANDED COPPER construction
with insulation properties permitted in accordance with the
system voltage, as follows:
a) less than 50 volts - SAE conductors are
permitted in addition to those for 50 volts and over. (See
183.430).
b) 50 volts or more - NEC, IEEE and UL conductors
are permitted. (See 183.435).
Previous | Next
|