Electrical
Systems
Manufacturer Requirements
FEDERAL LAW
183.410 - Ignition Protection
(b) An electrical component is isolated
from a gasoline fuel source if:
(3) The space between the electrical
component and the gasoline fuel source is at least
two feet and the space is open to the atmosphere.
|
This section deals with isolation of an electrical
component using open spaces and minimum
distances. The previous two sections discussed bulkheads,
and decks or special enclosures, respectively.
Ignition protection is not required for electrical
components that are in a space that is open to the atmosphere
and is located at least two feet from a gasoline fuel source.
The term “open to the atmosphere” is defined as
a space or a compartment having at least 15 square inches
of unobstructed area opening into the compartment for every
square foot of compartment volume. Open boats, such as runabouts,
with the engine aft and the fuel tank located far enough forward
to meet the two foot provision will be able to use non-ignition
protected components in their instrument panel. Figure 8 depicts
a typical open boat, whose bow compartment is open to the
atmosphere, with a two foot distance maintained between electrical
components and the gasoline fuel source. Figure 4 shows a
saddle tank installation with a two foot distance between
electrical components and the gasoline fuel source.
FIGURE
3 - Isolation of Electrical Components
FIGURE
4 - Isolation of Electrical Components
FIGURE
5 - Isolation of Electrical Components
FIGURE
6 - Isolation of Electrical Components
FIGURE
7 - Isolation of Electrical Components
Partial Bulkhead - Foot board, Toe board - In
figure 8a,b,c, we see how boat structures such as a partial
bulkhead may be fitted to increase the distance between the
source of fuel and the source of ignition.
FIGURE
8a - Isolation of Electrical Components
In figure 8a, the switches in the dashboard
are within 2’ of the fuel deck fitting, and also within
2’ of the fitting at the fuel tank. Each of these fittings
is a potential source of fuel leak. In this installation,
all switches would have to be ignition protected.
FIGURE
8b - Isolation of Electrical Components
Here the builder has fitted a partial bulkhead
across the boat, behind the dash to increase the distance
between the fuel deck fitting and the backside of the dash.
The builder has also decked over the front of the tank so
that the tank fitting is also more than 2’ from the
back of the dash.
FIGURE
8c - Isolation of Electrical Components
Here there are three potential sources
of fuel: The vent fitting in the side of the hull,
the fuel deck fitting, and the connections at the tank. The
vent and fill fittings are more than 2’ from the dashboard.
The tank fittings were too close to the dashboard. Here the
boat builder has installed a foot board to increase the separation
from the dashboard.
TO COMPLY WITH THE LAW
- Is each electrical component either
isolated or ignition protected?
|
Previous | Next
|